SC400 Greenhouse Controller

End-user manual for the greenhouse climate control system. This manual describes every settings screen and explains what each parameter does in plain language.

Measurement Screens

The measurement screens give a live overview of what the greenhouse is doing right now. All values are read-only — nothing can be changed here. Screens only appear when the relevant hardware is connected.

GREENHOUSE — MeasurementMeasurement
Temperature
Temp measurement21.4°C
Temp calculated setpoint22.0°C
Humidity humidity sensor only
Humidity74.5%
Humidity calculated setpoint80.0%
Heating heater only
Heating statusRunning
Heating signal65%
Heating c-setpoint100%
Fogging fog system only
Fogging statusStandby
Fog signal0%

Greenhouse Measurement — Temperature, Humidity, Heating, Fogging

This is the main overview screen for the greenhouse climate. It shows the current sensor readings alongside the setpoint the controller is aiming for (the calculated setpoint).

ValueUnitTypeWhat it shows
Temp measurement°CLiveCurrent inside air temperature measured by the sensor.
Temp calculated setpoint°CCalculatedThe temperature the controller is currently working towards, taking into account the active period and any slope transitions.
Humidity%LiveCurrent relative humidity inside the greenhouse.
Humidity c-setpoint%CalculatedThe humidity target for the current period.
Heating status—StatusCurrent state of the heating system: Off, Standby, or Running.
Heating signal%LiveHow hard the heater is currently working (0 = off, 100 = full output).
Heating c-setpoint%CalculatedThe target output level the heating controller is aiming for.
Fogging status—StatusCurrent state of the fog system: Off, Standby, or Fogging.
Fog signal%LiveCurrent fog output level.
GREENHOUSE — MeasurementMeasurement
Ventilation setpoint
Temp calculated ventilation24.5°C
Vent 1
Wind sideLeeward
Ventilation 1 statusOpening
Ventilation 135%
Ventilation 1 c-setpoint40%
Vent 2 if installed
Wind sideWindward
Ventilation 2 statusOpening
Ventilation 228%
Ventilation 2 c-setpoint30%
Ventilation total
Ventilation c-setpoint70%

Greenhouse Measurement — Ventilation

Shows the live status of all ventilation windows. The controller drives each window to its calculated setpoint; the actual opening follows as the motor moves.

ValueUnitTypeWhat it shows
Temp calculated ventilation°CCalculatedThe temperature at which ventilation is calculated to start opening. This is the temperature setpoint plus the ventilation addition offset.
Wind side—StatusWhether this window is currently behaving as the leeward (sheltered) or windward (exposed) side. The controller may switch sides based on wind direction.
Ventilation status—StatusCurrent window state: Closed, Opening, Open, Closing, or Blocked (e.g. by rain or storm).
Ventilation 1 / 2%LiveActual current opening of the window (0 = fully closed, 100 = fully open).
Ventilation c-setpoint%CalculatedThe target opening the controller is working towards, after applying all wind and rain limits.
Ventilation total c-setpoint%CalculatedCombined ventilation setpoint for both windows together (sum, max 200 %).
GREENHOUSE — Water HeatingMeasurement
Heating setpoint
Heating calculated setpoint22.0°C
Pipe min. setpoint
Pipe min. setpoint35.0°C
Pipe
Pipe measurement48.3°C
Pipe calculated setpoint52.0°C
Valve
Pipe pump statusRunning
Pipe servo position62%
Pipe servo calculated position65%
Grow Pipe grow pipe only
GrowPipe measurement38.1°C
GrowPipe calculated setpoint40.0°C
Grow pump statusRunning
GrowPipe servo position55%
GrowPipe servo calculated position58%

Greenhouse Measurement — Water Heating

Shows the live status of the hot-water pipe heating circuit. The heating pipe carries hot water from the boiler through the greenhouse; a mixing valve controls how much hot water enters the circuit to reach the pipe setpoint.

ValueUnitTypeWhat it shows
Heating c-setpoint°CCalculatedThe current air temperature target, used as the basis for all pipe temperature calculations.
Pipe min. setpoint°CCalculatedThe minimum pipe temperature calculated for this period, combining the period setting and any humidity influence.
Pipe measurement°CLiveActual water temperature measured in the heating pipe.
Pipe c-setpoint°CCalculatedThe pipe temperature the controller is working towards.
Pipe pump status—StatusWhether the circulation pump is running.
Pipe servo position%LiveCurrent position of the mixing valve (0 = all cool return water, 100 = all hot boiler water).
Pipe servo calculated position%CalculatedTarget valve position the controller is aiming for.
GrowPipe measurement°CLiveActual water temperature in the grow pipe (under-crop heating circuit).
GrowPipe c-setpoint°CCalculatedTarget temperature for the grow pipe circuit.
GREENHOUSE — Screens MeasurementMeasurement
Screen A
Screen A statusClosing
Screen A85%
Screen A c-setpoint100%
Screen B if installed
Screen B statusOpen
Screen B0%
Screen B c-setpoint0%

Greenhouse Measurement — Screens

Shows the live position and status of shade or energy screens. Screen A is typically the primary shade screen; Screen B (when fitted) is a second screen, often used as an energy screen at night.

ValueUnitTypeWhat it shows
Screen status—StatusCurrent screen state: Open, Closing, Closed, Opening, or Blocked (e.g. screen held open by wind or rain override).
Screen A / B%LiveActual screen position. 0 % = fully open (retracted), 100 % = fully closed (deployed).
Screen c-setpoint%CalculatedThe target position the controller is working towards, based on radiation, energy mode, or gap control.
Note A screen at 100 % is fully drawn (maximum shading or insulation). A gap of a few percent is sometimes held open deliberately to allow humidity to escape — this is controlled by the Screen Gap settings.
GREENHOUSE — CO2 MeasurementMeasurement
CO2 CO2 sensor only
CO2 statusDosing
CO2680ppm
CO2 calculated setpoint800ppm
Signal CO272%
Radiation radiation sensor only
Radiation542W/m²
Radiation c-setpoint542W/m²
Light Sum grow lights only
Light statusOff
Radiation sum1840J/cm²
Fan circulation fan only
Fan statusRunning
Hour count1 248h

Greenhouse Measurement — CO2, Radiation, Light & Fan

This screen groups the remaining climate measurements: CO2 concentration, solar radiation, the daily light sum used for grow-light control, and the recirculation fan.

ValueUnitTypeWhat it shows
CO2 status—StatusCurrent state of the CO2 system: Off (outside dosing window), Standby (within window, setpoint met), or Dosing (actively injecting CO2).
CO2ppmLiveCurrent measured CO2 concentration inside the greenhouse.
CO2 c-setpointppmCalculatedThe CO2 target for the current period, after applying any slope transitions.
Signal CO2%LiveCurrent CO2 dosing valve output level (diagnostic value).
RadiationW/m²LiveCurrent solar radiation measured inside or outside the greenhouse. Used by screen, CO2, and lighting control.
Radiation c-setpointW/m²CalculatedFiltered or processed radiation value used by the control algorithms.
Light status—StatusCurrent state of the grow lights: Off, On (assimilation), or On (day extension).
Radiation sumJ/cm²AccumulatedTotal radiation received today (natural + artificial). Resets at midnight. Used by the assimilation lighting programme to decide when enough light has been given.
Fan status—StatusWhether the recirculation fan is running.
Hour counthAccumulatedTotal running hours of the fan since the last reset.
GREENHOUSE — HeatersMeasurement
Heater A
Heater A statusRunning
Hour count3 412h
Heater B if installed
Heater B statusStandby
Hour count1 087h

Greenhouse Measurement — Heaters

Shows the operational status and cumulative running hours of each boiler or heat source. Heater A is the primary unit; Heater B is a second unit that switches on when Heater A alone is not enough to meet demand.

ValueUnitTypeWhat it shows
Heater status—StatusCurrent state of the heater: Off, Standby (waiting for minimum off-time), or Running.
Hour counthAccumulatedTotal hours this heater has been running since the last reset. Useful for scheduling maintenance intervals.
1. Temperature Control

The SC400 controls the greenhouse temperature using up to five time-based periods throughout the day. Each period has its own temperature target. The system transitions smoothly between periods using configurable slope rates. Period 1 is always active and serves as the base period when multiple periods are not configured.

GREENHOUSE  —  Temperature · Period 1 Settings
Temperature 22.0 °C
Min. pipe temperature Only shown when pipe heating is installed 0.0 °C
Humidity Only shown when humidity sensor is installed 80.0 %
Period timing Only shown in multi-period mode
Time method Astro Sunrise ▾
Start time to sunrise Active when Time method = Astro Sunrise +00:00 h:m
Start time to sunset Active when Time method = Astro Sunset +00:00 h:m
Start time Active when Time method = Absolute 00:00 h:m
Greyed rows appear only when the corresponding hardware or mode is active on this installation.

Temperature · Period 1 — Settings explained

This screen sets the target temperature for Period 1 — the primary setpoint that the greenhouse heating and ventilation system works to maintain. When only one period is used, this is the single target temperature for the entire day. When multiple periods are enabled, Period 1 is the fall-back period that applies whenever no other period is active (typically the night period).

Setting Range Default What it does
Temperature −15.0 to 45.0 °C 22.0 °C The inside temperature target for this period. The heating system activates when the measured temperature drops below this value; ventilation opens when it rises above it. Set this to the temperature you want the greenhouse to maintain during this period.
Min. pipe temperature pipe heating only 0.0 to 90.0 °C 0.0 °C Forces the heating pipe to stay at or above this temperature during this period, even if the air temperature is already at setpoint. This is useful for root-zone heating or preventing condensation. Set to 0 °C to leave the pipe temperature unforced.
Humidity humidity sensor only 0.0 to 100.0 % 80.0 % The target relative humidity for this period. Ventilation opens further if humidity exceeds this value, and the fog system can activate if humidity is significantly below it. 80 % is a typical starting point for most crops.
Time method multi-period mode only Off / Astro Sunrise / Astro Sunset / Absolute Astro Sunrise Determines how the start time for this period is defined. Choose Off to disable the period. See the time method table below for details.
Start time to sunrise Astro Sunrise only −4:00 to +4:00 h:m +00:00 Number of hours and minutes before (negative) or after (positive) sunrise at which this period becomes active. Example: −01:00 starts the period one hour before sunrise. The actual clock time changes automatically with the season.
Start time to sunset Astro Sunset only −4:00 to +4:00 h:m +00:00 Same as above but measured relative to sunset. Useful for setting an evening temperature that tracks the end of the natural light period.
Start time Absolute only 00:00 to 23:59 00:00 A fixed clock time at which this period starts every day, regardless of season. Use this when you want a consistent schedule that does not shift with sunrise or sunset.

Time method options:

OptionWhen to use it
Off The period is disabled and will never activate. Use this to skip a period you do not need.
Astro Sunrise The period starts relative to the calculated sunrise. Recommended for most growers because the transition follows the natural light cycle automatically throughout the year.
Astro Sunset The period starts relative to sunset. Useful for an evening period that matches the end of the day-light period.
Absolute The period starts at a fixed clock time. Use this only when the schedule must be independent of the season, for example for supplemental lighting programmes with fixed hours.
How multiple periods work together The controller checks all active periods every second. The period whose start time has most recently passed becomes the active period. Period 1 is the default: if no other period has started yet, Period 1 applies. A typical daily programme might be: Period 1 = 18 °C night (no start time needed — it is the default), Period 2 = 22 °C starting at sunrise − 01:00, Period 3 = 20 °C starting at sunset + 01:00. The Slope Up and Slope Down settings on the Periods overview screen control how quickly the setpoint changes when switching between periods.
GREENHOUSE — Temperature · PeriodsSettings
Rel temp alarm +/-5.0°C
Slope Up0.0°C/h
Slope Down0.0°C/h
Rel humidity alarm +/- humidity sensor only5.0%

Temperature · Periods — Settings explained

This screen controls how the setpoint transitions between periods and when temperature alarms are triggered. These settings apply to all five periods.

SettingRangeDefaultWhat it does
Rel temp alarm +/-1.0 – 25.0 °C5.0 °CAn alarm is raised if the measured temperature deviates more than this amount above or below the calculated setpoint. For example, with a setpoint of 22 °C and an alarm of 5 °C, an alarm fires if the temperature goes below 17 °C or above 27 °C.
Slope Up0.0 – 20.0 °C/h0.0Maximum rate at which the setpoint may rise when switching to a warmer period. A value of 2.0 °C/h means the setpoint increases by no more than 2 °C per hour, giving a gentle warm-up. Set to 0 to switch instantly.
Slope Down0.0 – 20.0 °C/h0.0Maximum rate at which the setpoint may fall when switching to a cooler period. Works the same way as Slope Up but for decreasing transitions.
Rel humidity alarm +/- humidity sensor only1.0 – 75.0 %5.0 %An alarm is raised if the measured humidity deviates more than this percentage from the humidity setpoint.
Tip — Slope values Slopes prevent temperature stress on plants. A common setting is 2–4 °C/h for rise and fall. Setting both to 0 means the setpoint jumps instantly when a period changes, which can cause aggressive heating or ventilation responses.
GREENHOUSE — Temperature · Period 2Settings
Time methodAstro Sunrise ▾
Temperature Active when time method ≠ Off12.0°C
Min. pipe temperature pipe heating only0.0°C
Humidity humidity sensor only80.0%
Start time to sunrise Astro Sunrise mode+00:00h:m
Start time to sunset Astro Sunset mode+00:00h:m
Start time Absolute mode12:00h:m

Temperature · Period 2 — Settings explained

Period 2 defines a second temperature target that becomes active at a configured time. When the Time method is set to Off, this period is disabled and has no effect. The setpoint and start-time fields are greyed out when the period is off.

SettingRangeDefaultWhat it does
Time methodOff / Astro Sunrise / Astro Sunset / AbsoluteAstro SunriseSelects how the start time is defined, or disables this period entirely. See Period 1 for a full description of each option.
Temperature−15.0 – 45.0 °C12.0 °CThe temperature target while this period is active.
Min. pipe temperature pipe heating only0.0 – 90.0 °C0.0 °CMinimum pipe temperature during this period. See Period 1 for details.
Humidity humidity sensor only0.0 – 100.0 %80.0 %Humidity target during this period.
Start time to sunrise−4:00 – +4:00+00:00Offset from sunrise at which this period activates (Astro Sunrise mode only).
Start time to sunset−4:00 – +4:00+00:00Offset from sunset at which this period activates (Astro Sunset mode only).
Start time00:00 – 23:5912:00Fixed daily start time (Absolute mode only).
GREENHOUSE — Temperature · Period 3Settings
Time methodAstro Sunrise ▾
Temperature12.0°C
Min. pipe temperature pipe heating only0.0°C
Humidity humidity sensor only80.0%
Start time to sunrise+00:00h:m
Start time to sunset+00:00h:m
Start time12:00h:m

Temperature · Period 3 — Settings explained

Period 3 has the same structure as Period 2. All settings work identically — refer to Period 2 for full descriptions. A typical use is a mid-morning period with a slightly higher temperature once the crop has warmed up after sunrise.

GREENHOUSE — Temperature · Period 4Settings
Time methodAstro Sunrise ▾
Temperature12.0°C
Min. pipe temperature pipe heating only0.0°C
Humidity humidity sensor only80.0%
Start time to sunrise+00:00h:m
Start time to sunset+00:00h:m
Start time12:00h:m

Temperature · Period 4 — Settings explained

Period 4 has the same structure as Periods 2 and 3. All settings work identically — refer to Period 2 for full descriptions. Typically used for an afternoon or early-evening temperature target.

GREENHOUSE — Temperature · Period 5Settings
Time methodAstro Sunrise ▾
Temperature12.0°C
Min. pipe temperature pipe heating only0.0°C
Humidity humidity sensor only80.0%
Start time to sunrise+00:00h:m
Start time to sunset+00:00h:m
Start time12:00h:m

Temperature · Period 5 — Settings explained

Period 5 is the last available period and works identically to Periods 2–4. All settings and options are the same — refer to Period 2 for full descriptions. Typically used for a late-evening or night cool-down target.

2. Ventilation

The ventilation system opens and closes ridge windows to control temperature and humidity. The controller calculates a target opening percentage every minute and drives the window motors towards it. Wind speed and direction are taken into account to protect the structure.

GREENHOUSE — VentilationSettings
Temperature addition2.5°C
P-Band5.0°C
Damping outside temp20.0°C
Reaction of windowNormal ▾

Ventilation — Settings explained

These four settings define the core behaviour of the ventilation controller: when it starts to open and how quickly it responds to temperature changes.

SettingRangeDefaultWhat it does
Temperature addition 0.0 – 20.0 °C 2.5 °C The number of degrees above the current temperature setpoint at which the windows start to open. For example, if the setpoint is 20 °C and the addition is 2.5 °C, ventilation begins opening when the temperature reaches 22.5 °C. A larger value means the greenhouse runs warmer before windows open.
P-Band 0.5 – 25.0 °C 5.0 °C The proportional band of the ventilation controller. The window opens from 0 % to 100 % as the temperature rises across this band above the opening threshold. A narrow P-Band (e.g. 2 °C) gives a more aggressive response; a wide band (e.g. 10 °C) gives a slower, smoother response.
Damping outside temp 0.1 – 80.0 °C 20.0 °C Compensates for hot outside air. If the outside temperature is high, fully open windows would bring in hot air and overshoot the setpoint. This value limits how far the windows open when the outside temperature is close to the inside setpoint. A larger value means less compensation (windows open more freely).
Reaction of window Old / Slow / Normal / Fast Normal Controls the speed of the ventilation motor response. Slow makes small corrections at long intervals, reducing wear and preventing hunting. Fast makes larger corrections more frequently, useful when temperature changes are rapid. Old uses the original algorithm for backwards compatibility.
Tip — Finding the right P-Band If the temperature overshoots (windows open too far and then swing back), increase the P-Band. If the temperature is slow to come down, decrease the P-Band or reduce the Temperature addition.
GREENHOUSE — Venti. SenseSettings
Dead zone1.0%
Calculation interval01:00min

Ventilation Sense — Settings explained

These two settings fine-tune how sensitive the ventilation controller is to small changes, preventing unnecessary motor movement.

SettingRangeDefaultWhat it does
Dead zone 0.0 – 35.0 % 1.0 % The minimum change in calculated opening before the motor is commanded to move. If the new calculated setpoint is within this percentage of the current position, the motor stays still. This prevents constant small adjustments that cause wear without meaningfully affecting the climate. A value of 1 % is a good starting point.
Calculation interval 1 – 20 min 1 min How often the controller recalculates the ventilation setpoint and potentially commands the motor. A longer interval (e.g. 5 min) gives the temperature more time to stabilise after a window move before another correction is made, reducing hunting in slow-responding greenhouses.
GREENHOUSE — HumiditySettings
Humidity diff0.0%
Max Opening0%

Humidity — Settings explained

When humidity rises above the setpoint by more than the configured difference, the ventilation windows open to let moist air out. This screen sets how much extra the windows can open for humidity removal, independently of the temperature control.

SettingRangeDefaultWhat it does
Humidity diff 0.0 – 100.0 % 0.0 % The humidity must exceed the period setpoint by at least this amount before ventilation opens for humidity removal. For example, if the humidity setpoint is 80 % and this value is 5 %, humidity ventilation activates above 85 %. Set to 0 to disable humidity-driven ventilation.
Max Opening 0 – 100 % 0 % The maximum additional window opening allowed for humidity control. The windows will not open further than this value purely for humidity purposes, even if humidity remains high. This prevents excessive cold air from entering on cold days when humidity is also high.
Tip Set Max Opening to 20–30 % as a starting point. This allows enough ventilation to lower humidity without letting in too much cold outside air when the temperature is already at setpoint.
GREENHOUSE — Ventilation WindSettings
Start Wind Trajectory1.5m/s
End Wind Trajectory8.0m/s
Max. Vent. decrease Wind70%
Sync window to 0% at+00:00h:m
Only sync window below10%
Use slow wind directionNo ▾

Ventilation Wind — Settings explained

Wind can damage open windows or create uneven ventilation. These settings reduce the window opening proportionally as wind speed increases, and let you sync windows to a known closed position once per day.

SettingRangeDefaultWhat it does
Start Wind Trajectory 0.0 – 17.1 m/s 1.5 m/s The wind speed at which the controller begins reducing the window opening. Below this speed, wind has no effect on the ventilation setpoint.
End Wind Trajectory 0.0 – 17.1 m/s 8.0 m/s The wind speed at which the maximum reduction has been applied. Between Start and End, the reduction increases linearly. Above End, the maximum reduction is held constant.
Max. Vent. decrease Wind 0 – 100 % 70 % The maximum amount by which wind can reduce the calculated ventilation setpoint. For example, if the temperature demands 80 % opening and this value is 70 %, the maximum reduction is 56 % (70 % of 80 %), leaving at least 24 % open.
Sync window to 0% at −4:00 – +4:00 (sunset offset) +00:00 Once per day, at this time relative to sunset, the controller drives all windows to fully closed to recalibrate the motor position counter. This corrects any drift that builds up over the day. Set to 0 to sync at sunset.
Only sync window below 0 – 100 % 10 % The sync only happens if the calculated setpoint is at or below this percentage at the sync time. This prevents a forced close when the greenhouse still needs ventilation (e.g. on a hot evening).
Use slow wind direction No / Yes No When set to Yes, the controller uses a heavily filtered (slow-responding) wind direction signal to decide which side is leeward and which is windward. This prevents the sides from switching rapidly when the wind direction is fluctuating.
GREENHOUSE — Ventilation LeeWardSettings
Abs. Storm Position5%
Max. position Rain30%
Maximum position100%
Minimum position0%

Ventilation Leeward — Settings explained

The leeward side is the window on the sheltered side of the greenhouse (away from the wind). Because it is protected, it can generally open further than the windward side without risk of damage. These settings define the position limits that apply to the leeward window under different weather conditions.

SettingRangeDefaultWhat it does
Abs. Storm Position 0 – 25 % 5 % The maximum opening allowed during a storm condition. Even if the temperature demands more ventilation, the window will not open beyond this position when storm wind speeds are detected. This protects the structure and crop from storm damage.
Max. position Rain 0 – 100 % 30 % The maximum opening allowed when rain is detected. Rain entering an open window can damage the crop or cause disease. This limit reduces the opening to keep rain out while still allowing some ventilation.
Maximum position 0 – 100 % 100 % The absolute maximum opening under normal (no rain, no storm) conditions. Setting this below 100 % is useful if the window mechanism has a physical limit, or if you want to reduce draughts in sensitive crop areas near the window.
Minimum position 0 – 100 % 0 % The window will never close below this position, even when the temperature is at or below setpoint. A small minimum (e.g. 5 %) ensures a permanent base ventilation to prevent stagnant air and disease pressure.
GREENHOUSE — Ventilation WindWardSettings
Abs. Storm Position0%
Max. position Rain30%
Maximum position100%
Minimum position0%
Following0%

Ventilation Windward — Settings explained

The windward side faces into the wind and is more exposed. It typically needs tighter position limits than the leeward side. An additional Following setting allows the windward window to track the leeward window proportionally.

SettingRangeDefaultWhat it does
Abs. Storm Position 0 – 25 % 0 % Maximum opening during a storm. The windward side is more vulnerable, so this is typically set lower than the leeward storm position — often 0 % to keep the windward window fully closed in a storm.
Max. position Rain 0 – 100 % 30 % Maximum opening when rain is detected. Rain drives directly into windward windows, so this is often set lower than the leeward rain limit.
Maximum position 0 – 100 % 100 % Absolute maximum opening in normal conditions. Refer to the Leeward description for details.
Minimum position 0 – 100 % 0 % The window never closes below this position. Refer to the Leeward description for details.
Following 0 – 100 % 0 % When set above 0, the windward window opens to this percentage of the leeward window's position, rather than calculating its own setpoint from temperature. For example, if set to 80 % and the leeward window is at 50 %, the windward window targets 40 %. This is useful when wind direction varies and you want both sides to open together proportionally.
3. Heating

The heating system uses one or two boilers (Heater A and B) connected to a hot-water pipe circuit. The controller switches heaters on and off based on the temperature setpoint, with configurable minimum on/off times to protect the boiler.

GREENHOUSE — HeatingSettings
Minimum ON time10min
Minimum OFF time10min
Temp deadzone Heater A Heater A only3.0°C
Temp deadzone Heater B Heater B only4.0°C

Heating — Settings explained

These settings control how and when each boiler switches on and off. The minimum times protect the boiler from short-cycling (rapid on/off switching which causes wear). The deadzone settings stagger the two heaters so they do not both switch on at the same moment.

SettingRangeDefaultWhat it does
Minimum ON time 5 – 90 min 10 min Once a heater switches on, it stays on for at least this many minutes before it is allowed to switch off again, even if the setpoint is already reached. This prevents short bursts that waste energy and cause boiler wear.
Minimum OFF time 5 – 90 min 10 min Once a heater switches off, it stays off for at least this many minutes before it can switch on again. This prevents the boiler from re-igniting immediately after a short run, which is hard on burner components.
Temp deadzone Heater A Heater A only 0.5 – 10.0 °C 3.0 °C Heater A switches on when the measured temperature drops this many degrees below the current setpoint. For example, with a setpoint of 20 °C and a deadzone of 3 °C, Heater A starts at 17 °C. A larger deadzone means the heater waits longer before switching on.
Temp deadzone Heater B Heater B only 0.5 – 10.0 °C 4.0 °C Same as Heater A but for the second boiler. Setting Heater B's deadzone larger than Heater A's (e.g. 4 °C vs 3 °C) means Heater B only activates when the temperature has dropped further, making it a backup that only engages when one boiler is not enough.
Tip — Staggering the deadzones Always set Heater B's deadzone 1–2 °C larger than Heater A's. This ensures Heater A carries the normal heating load and Heater B only assists during cold periods or after a sudden setpoint increase.
4. Lighting

The SC400 can control supplemental grow lights in three programmes: Day Extension (extends the photoperiod before sunrise and/or after sunset), Assimilation (adds light when natural radiation is insufficient during the day), and Photo Period (fixed on/off cycles). Only one programme is active at a time.

GREENHOUSE — LightSettings
ProgramDay Extension ▾
PowerGroup 1 ▾
Disable at radiation not used in Photo Period mode3 900J/cm²

Light — Settings explained

This screen selects the lighting programme and the global radiation threshold above which lights are switched off to avoid adding unnecessary heat when there is plenty of natural light.

SettingRangeDefaultWhat it does
Program Off / Day Extension / Assimilation / Photo Period Off Selects how the lights are controlled. Off disables all grow lights. Day Extension runs the lights for a set duration before sunrise and/or after sunset to extend the daily light period. Assimilation runs lights during the day whenever natural radiation falls below a threshold. Photo Period runs the lights on a fixed repeating on/off cycle, independent of natural light.
Power Group 1 – Group 4 Group 1 Selects which group of light rows is used. Each group corresponds to a set of lighting rows configured on the Light Row screen. This allows different intensity levels to be pre-configured and quickly switched between.
Disable at radiation 1 – 1 250 J/cm² 3 900 J/cm² When the accumulated daily radiation sum (natural light received today) exceeds this value, the lights are switched off for the rest of the day. This prevents unnecessary electricity use when the crop has already received enough light. Not applicable in Photo Period mode.
GREENHOUSE — Light Day ExtensionSettings
Before sunrise
Start time to sunrise+00:00h:m
Duration00:00h:m
After sunset
Start time to sunset+00:00h:m
Duration00:00h:m

Light Day Extension — Settings explained

In Day Extension mode, the lights run for a fixed duration before sunrise and/or after sunset to give the crop a longer daily light period. Both periods can be configured independently — use one or both depending on your crop's needs.

SettingRangeDefaultWhat it does
Start time to sunrise −4:00 – +4:00 +00:00 When the morning light period begins, expressed as an offset from sunrise. A negative value (e.g. −02:00) starts the lights 2 hours before sunrise. Set to 0:00 to disable the morning extension.
Duration (morning) 00:00 – 23:59 00:00 How long the lights stay on in the morning extension period. The lights switch off after this duration, regardless of sunrise. Set to 0:00 to disable.
Start time to sunset −4:00 – +4:00 +00:00 When the evening light period begins, expressed as an offset from sunset. A positive value (e.g. +00:30) starts the lights 30 minutes after sunset. Set to 0:00 to disable the evening extension.
Duration (evening) 00:00 – 23:59 00:00 How long the lights stay on in the evening extension period. Set to 0:00 to disable.
Example To extend the day by 2 hours each morning: set Start time to sunrise to −02:00 and Duration to 02:00. The lights will turn on 2 hours before sunrise and switch off at sunrise.
GREENHOUSE — Light AssimilationSettings
Start time to sunrise+00:00h:m
End time to sunset+00:00h:m
Radiation limit900W/m²

Light Assimilation — Settings explained

In Assimilation mode the lights run during the day, but only when natural solar radiation falls below a set threshold. The light period is bounded by configurable sunrise and sunset offsets — outside this window the lights stay off regardless of radiation.

SettingRangeDefaultWhat it does
Start time to sunrise −4:00 – +4:00 +00:00 The earliest the assimilation lights may switch on, expressed as an offset from sunrise. A negative value allows the lights to start before sunrise if radiation is already low. Set to 0:00 to allow lights from sunrise onwards.
End time to sunset −4:00 – +4:00 +00:00 The latest the assimilation lights may stay on, expressed as an offset from sunset. A negative value (e.g. −01:00) switches the lights off one hour before sunset. Set to 0:00 to allow lights until sunset.
Radiation limit 0 – 1 200 W/m² 900 W/m² The solar radiation level below which the lights switch on. When natural radiation drops below this value (e.g. on a cloudy day), the lights activate to compensate. When radiation rises above it again, the lights switch off. A typical value is 700–900 W/m².
Note The global Disable at radiation setting on the Light screen (in J/cm² daily sum) also applies: if the daily light sum has already been reached, assimilation lights will not switch on even if the current radiation is below the limit.
GREENHOUSE — Light Photo PeriodSettings
Number of periods2
Period On01:00h:m
Period Off01:00h:m

Light Photo Period — Settings explained

In Photo Period mode the lights cycle on and off repeatedly throughout the day at a fixed rhythm, regardless of natural light levels. This is used for crops that need a specific light/dark pattern to control flowering.

SettingRangeDefaultWhat it does
Number of periods 1 – 100 2 How many complete on/off cycles run per day. For example, with Period On = 1:00 and Period Off = 1:00, one cycle lasts 2 hours. Setting 12 periods gives 12 × 2 h = 24 h of cycling, covering the full day.
Period On 00:05 – 23:59 01:00 The duration each cycle keeps the lights on. The cycle begins at midnight and the first On period starts immediately.
Period Off 00:05 – 23:59 01:00 The duration each cycle keeps the lights off. After each On period the lights switch off for this duration before the next On period begins.
5. Fans

The recirculation fan keeps air moving inside the greenhouse to even out temperature and humidity gradients. In Auto mode the controller switches the fan on or off based on the difference between inside and outside conditions.

GREENHOUSE — FansSettings
Fan modeAuto ▾
Start time Auto mode only12:00h:m
End time Auto mode only12:00h:m
Temperature diff Auto mode only3.0°C
Outside temp off Auto mode only, if sensor present-4.0°C
Humidity diff Auto mode only4.0%

Fans — Settings explained

The fan mode and the conditions under which the fan runs in Auto mode are configured here. All settings below Fan mode are only active when Auto is selected.

SettingRangeDefaultWhat it does
Fan mode Off / On / Auto Off Off keeps the fan permanently off. On runs the fan continuously. Auto switches the fan on and off based on the conditions configured below.
Start time 00:00 – 23:59 12:00 In Auto mode, the fan will only run between Start time and End time. Outside this window it stays off regardless of temperature or humidity conditions.
End time 00:00 – 23:59 12:00 The time at which the daily fan window closes. After this time the fan switches off until the next Start time.
Temperature diff 0.0 – 45.0 °C 3.0 °C The fan switches on when the inside temperature is this many degrees warmer than the outside temperature. This ensures the fan runs when there is a meaningful temperature gradient to equalize, and stays off when inside and outside temperatures are similar.
Outside temp off outside sensor only −45.0 – 0.0 °C −4.0 °C The fan switches off if the outside temperature falls below this value, even if the temperature difference condition is met. This prevents cold outside air from being mixed in during very cold weather.
Humidity diff 0.0 – 10.0 % 4.0 % The fan also switches on when the inside humidity exceeds the setpoint by this amount. This helps remove excess moisture even when there is no significant temperature difference.
GREENHOUSE — FansSettings
On at screen higher screen only, Auto mode40%
Off at ventilation higher ventilation only, Auto mode40%
On while fogging fog system only, Auto modeYes ▾
Max. CO2 fan on CO2 sensor only, Auto mode1 250ppm
Min. CO2 fan off CO2 sensor only, Auto mode350ppm

Fans Conditions — Settings explained

This second fans screen configures additional conditions that interact with other greenhouse systems. All rows are conditional — they only appear when the relevant hardware or system is active.

SettingRangeDefaultWhat it does
On at screen higher screen only 0 – 100 % 40 % The fan switches on automatically when the shade screen is closed beyond this percentage. A closed screen reduces natural air circulation, so the fan compensates to prevent hot spots and humidity build-up under the screen.
Off at ventilation higher ventilation only 0 – 100 % 40 % The fan switches off when the ventilation windows are open beyond this percentage. When windows are wide open, natural air movement is sufficient and running the fan would be redundant and noisy.
On while fogging fog system only No / Yes Yes When set to Yes, the fan runs continuously while the fog system is active. The fan distributes the fog evenly throughout the greenhouse and prevents it from settling in concentrated pools near the nozzles.
Max. CO2 fan on CO2 sensor only 1 000 – 5 000 ppm 1 250 ppm The fan switches on when CO2 exceeds this level. Running the fan when CO2 is high helps distribute CO2 evenly around the crop and prevents pockets of stale air near the floor.
Min. CO2 fan off CO2 sensor only 250 – 4 500 ppm 350 ppm Once the fan has switched on due to high CO2, it stays on until CO2 drops below this level. This hysteresis prevents the fan from rapidly switching on and off when CO2 is hovering near the upper threshold.
6. CO2

The SC400 supports two CO2 control methods. When a CO2 sensor is installed, the system doses to maintain a measured setpoint across up to three time-based periods. When no sensor is present, an interval timer (CO2 Interval) doses for a fixed on/off cycle during the day, using the boiler flue gas as the CO2 source.

GREENHOUSE — CO2 · IntervalSettings
Enable AUTO intervalOn ▾
Start to sunrise when enabled+00:00h:m
End to sunset when enabled+00:00h:m
Dose ON time when enabled10min
Dose OFF time when enabled10min
Enable from radiation sensor only, when enabled870W/m²

CO2 Interval — Settings explained

This screen appears only on installations without a CO2 sensor, where the boiler flue gas (containing CO2) is routed into the greenhouse. Because there is no feedback measurement, the system doses on a simple timed cycle within a configurable daily window.

SettingRangeDefaultWhat it does
Enable AUTO interval Off / On On Switches the timed CO2 dosing on or off. When Off, no CO2 is dosed regardless of the other settings.
Start to sunrise −4:00 – +4:00 +00:00 The daily dosing window opens at this offset from sunrise. CO2 will not dose before this time, even if the interval timer is active.
End to sunset −4:00 – +4:00 +00:00 The daily dosing window closes at this offset from sunset. CO2 stops dosing at this time regardless of the interval cycle.
Dose ON time 1 – 90 min 10 min How many minutes the CO2 valve stays open during each dose cycle. Longer on-times deliver more CO2 per cycle.
Dose OFF time 1 – 90 min 10 min How many minutes the CO2 valve stays closed between dose cycles. This gives the CO2 time to distribute through the greenhouse before the next dose.
Enable from radiation sensor only 25 – 1 100 W/m² 870 W/m² CO2 dosing only starts when solar radiation is above this threshold. Plants absorb CO2 faster in bright light; dosing in low light or darkness is wasteful. This setting prevents CO2 from being released when the crop cannot use it.
GREENHOUSE — CO2 · Period 1Settings
CO2 Setpoint250ppm
Enable from radiation sensor only870W/m²
Time methodAstro Sunrise ▾
Start time to sunrise Astro Sunrise mode+00:00h:m
Start time to sunset Astro Sunset mode+00:00h:m
Start time Absolute mode12:00h:m
Slope Up active when time method ≠ Off0ppm/h
Slope Down active when time method ≠ Off0ppm/h

CO2 · Period 1 — Settings explained

CO2 dosing uses up to three time-based periods, each with its own setpoint. Period 1 is the base period (typically the main daytime period). The time method and slope settings work exactly like the temperature periods — refer to the Temperature chapter for a detailed explanation of those options.

SettingRangeDefaultWhat it does
CO2 Setpoint 0 – 1 000 ppm 250 ppm The CO2 concentration the system will dose to maintain during this period. The controller doses CO2 when the measured level falls below this value. Typical greenhouse enrichment targets are 600–1 000 ppm depending on crop and ventilation rate.
Enable from radiation sensor only 25 – 1 100 W/m² 870 W/m² CO2 dosing only activates when solar radiation is above this threshold. Plants absorb CO2 through photosynthesis which requires light — dosing in darkness is wasteful. This setting prevents unnecessary CO2 use at night or during very cloudy periods.
Time method Off / Astro Sunrise / Astro Sunset / Absolute Astro Sunrise Determines when this period becomes active. See the Temperature chapter for a full explanation of each option.
Start time to sunrise / sunset / absolute various +00:00 The start time of this period, defined as an offset from sunrise, offset from sunset, or a fixed clock time — depending on the Time method selected.
Slope Up 0 – 500 ppm/h 0 ppm/h Maximum rate at which the CO2 setpoint may rise when transitioning to this period from a lower setpoint. Set to 0 for an instant switch.
Slope Down 0 – 500 ppm/h 0 ppm/h Maximum rate at which the CO2 setpoint may fall when transitioning away from this period to a lower setpoint. Set to 0 for an instant switch.
GREENHOUSE — CO2 · Period 2Settings
Time methodAstro Sunrise ▾
CO2 active when time method ≠ Off550ppm
Start time to sunrise+00:00h:m
Start time to sunset+00:00h:m
Start time20:00h:m
Slope Up0ppm/h
Slope Down0ppm/h

CO2 · Period 2 — Settings explained

Period 2 has the same structure as Period 1. Set Time method to Off to disable this period. All settings work identically to Period 1 — refer there for full descriptions. A typical use is a higher CO2 setpoint (e.g. 800 ppm) during peak growing hours and a lower setpoint at other times.

GREENHOUSE — CO2 · Period 3Settings
Time methodAstro Sunset ▾
CO2 active when time method ≠ Off0ppm
Start time to sunrise+00:00h:m
Start time to sunset+00:00h:m
Start time12:00h:m
Slope Up0ppm/h
Slope Down0ppm/h

CO2 · Period 3 — Settings explained

Period 3 is the third and final CO2 period. It works identically to Periods 1 and 2 — refer to Period 1 for full descriptions. Period 3 defaults to Astro Sunset timing with a setpoint of 0 ppm, making it a convenient end-of-day period that stops dosing after sunset.

GREENHOUSE — CO2 · SystemSettings
Percent heaters to use100%
CO2 dead zone CO2 sensor only30ppm
CO2 Alarm CO2 sensor only2 000ppm
Max. temperature35.0°C

CO2 System — Settings explained

This screen contains system-wide CO2 settings that apply regardless of which period is active. It also links CO2 dosing to the heating system, since many installations use boiler flue gas as the CO2 source.

SettingRangeDefaultWhat it does
Percent heaters to use 25 – 100 % 100 % When the boiler flue gas is used as the CO2 source, this setting limits how much of the heating output can be "borrowed" for CO2 dosing. For example, setting 75 % means only 75 % of the total heating capacity will be used for CO2 production — the rest remains available purely for heating. This prevents over-heating the greenhouse when CO2 demand is high.
CO2 dead zone CO2 sensor only 25 – 750 ppm 30 ppm The CO2 level must fall this many ppm below the setpoint before dosing starts. Once dosing starts, it continues until the setpoint is reached. This prevents the dosing valve from opening and closing rapidly when CO2 is hovering near the setpoint.
CO2 Alarm CO2 sensor only 1 000 – 8 000 ppm 2 000 ppm An alarm is triggered if the measured CO2 concentration rises above this level. Excessively high CO2 (above ~2 000 ppm) can indicate a dosing malfunction or inadequate ventilation and may be harmful to workers entering the greenhouse.
Max. temperature 15.0 – 50.0 °C 35.0 °C CO2 dosing is automatically suspended if the inside temperature exceeds this value. When it is very hot, the ventilation windows need to be open to cool the greenhouse — open windows allow CO2 to escape, making dosing pointless and wasteful.
7. Pipe Heating System

The pipe heating system circulates hot water from the boiler through pipes inside the greenhouse. A motorised mixing valve blends hot and return water to maintain the pipe at the correct temperature. The controller uses a proportional-integral (PI) algorithm to position the valve.

GREENHOUSE — Heating SystemSettings
Heating addition-5.0°C
Max. pipe temperature60.0°C
Pipe / Heating ref.35.0°C
Pipe temp I-Time30s
Valve I-Time30s
Valve P-Band10.0°C

Heating System — Settings explained

These settings control the behaviour of the hot-water pipe circuit and its mixing valve. They are technical parameters that rarely need to be changed once the system is commissioned.

SettingRangeDefaultWhat it does
Heating addition −35.0 – −0.1 °C −5.0 °C The pipe heating circuit starts working when the air temperature falls this many degrees below the current air temperature setpoint. For example, with a setpoint of 20 °C and an addition of −5 °C, the pipe circuit activates when the air temperature drops to 15 °C. A smaller negative value (e.g. −2 °C) makes the system respond earlier.
Max. pipe temperature 30.0 – 90.0 °C 60.0 °C The absolute maximum temperature the pipe is allowed to reach. This protects the pipes, fittings, and any crop in contact with the pipes from damage due to excessive heat.
Pipe / Heating ref. 2.0 – 50.0 °C 35.0 °C The reference temperature difference used to scale the pipe temperature setpoint relative to the air setpoint. This is an installation-specific calibration value that links the pipe curve to the actual heat output of the system.
Pipe temp I-Time 0 – 10 000 s 30 s The integration time of the pipe temperature controller. A longer I-Time makes the controller slower to respond to temperature errors but avoids overshooting the pipe setpoint.
Valve I-Time 0 – 10 000 s 30 s The integration time of the mixing valve position controller. This controls how quickly the valve moves to reach the target position. A longer time results in slower, smoother valve movement.
Valve P-Band 1.0 – 30.0 °C 10.0 °C The proportional band of the mixing valve controller. The valve moves from 0 % to 100 % as the pipe temperature error grows across this band. A wider P-Band gives smoother but slower valve response.
GREENHOUSE — Heating SystemSettings
Humid. inf. min. pipe10.0°C
Humid. max. addition10.0°C

Heating System — Humidity Influence on Pipe

When humidity is high, a warmer pipe can help drive moisture out of the crop canopy. These two settings allow the minimum pipe temperature (set per period) to be automatically raised when the measured humidity exceeds its setpoint.

SettingRangeDefaultWhat it does
Humid. inf. min. pipe 0.0 – 10.0 °C 10.0 °C The scale factor that determines how strongly high humidity raises the minimum pipe temperature. A value of 10.0 °C means that when humidity is at its maximum deviation above setpoint, the minimum pipe temperature is raised by up to the Humid. max. addition value. A lower value reduces the influence of humidity on pipe temperature.
Humid. max. addition 0.0 – 20.0 °C 10.0 °C The maximum number of degrees that the minimum pipe temperature can be raised due to high humidity. For example, if the period's minimum pipe temperature is 30 °C and this value is 10 °C, the pipe minimum can be raised to at most 40 °C when humidity is very high.
How it works together If humidity is 5 % above setpoint and Humid. inf. min. pipe is 10 °C: the addition is (5/10) × max. addition. So with max. addition = 10 °C, the pipe minimum rises by 5 °C. The warmer pipe evaporates moisture from the crop and the greenhouse structure, helping to bring humidity back down.
GREENHOUSE — GrowPipesSettings
Max. growpipe temp30.0°C
Min. growpipe temp30.0°C
Valve I-Time30s
Valve P-Band10.0°C

GrowPipes — Settings explained

Grow pipes run close to or under the crop and maintain a lower, more stable water temperature than the main heating pipes. They provide root-zone warmth without overheating the air. The controller uses a mixing valve with PI control to hold the grow pipe at the configured temperature range.

SettingRangeDefaultWhat it does
Max. growpipe temp 20.0 – 39.0 °C 30.0 °C The upper limit for the grow pipe water temperature. The mixing valve will never allow the grow pipe to exceed this temperature, protecting the root zone from heat stress.
Min. growpipe temp 20.0 – 39.0 °C 30.0 °C The lower limit for the grow pipe water temperature. The controller will maintain at least this temperature in the grow pipe circuit at all times when the system is active, ensuring a minimum level of root-zone warmth even when the air setpoint is already met.
Valve I-Time 0 – 10 000 s 30 s The integration time of the grow pipe mixing valve controller. Controls the speed of valve adjustment. Refer to the Heating System screen for a full description.
Valve P-Band 1.0 – 30.0 °C 10.0 °C The proportional band of the mixing valve controller. Refer to the Heating System screen for a full description.
8. Screens

The SC400 controls up to two motorised screens (A and B). Each screen has three independent control modes that work simultaneously: Radiation (shade during bright sunlight), Energy (insulation at night), and Gap (small opening for humidity removal). The screen position is the highest demand from all active modes.

GREENHOUSE — Screen A RadiationSettings
Start to sunrise+01:00h:m
End to sunset-01:00h:m
Radiation above 100%1 000W/m²
Radiation below 100%0W/m²
Radiation for position900W/m²
Screen position active when Radiation for position > 080%

Screen A Radiation — Settings explained

The radiation mode closes Screen A during bright sunlight to protect the crop from heat and light stress. The screen closes proportionally as radiation rises, and opens again as radiation falls. A time window limits radiation control to daylight hours only.

SettingRangeDefaultWhat it does
Start to sunrise −4:00 – +4:00 +01:00 The radiation screen control becomes active at this offset after sunrise. Setting +01:00 means the screen will not respond to radiation until one hour after sunrise, giving time for the greenhouse to warm up naturally in the morning.
End to sunset −4:00 – +4:00 −01:00 The radiation screen control deactivates at this offset before sunset. Setting −01:00 means the screen opens one hour before sunset, allowing the afternoon sun in as temperatures drop.
Radiation above 100% 0 – 1 200 W/m² 1 000 W/m² When radiation rises above this level the screen closes fully (100 %). This is the main shading threshold — set it to the radiation level at which crop heat stress begins.
Radiation below 100% 0 – 250 W/m² 0 W/m² When radiation falls below this level the screen opens fully (0 %). This creates a hysteresis gap between the closing threshold and the opening threshold, preventing the screen from continuously opening and closing when radiation fluctuates around the main threshold. Set to 0 to disable hysteresis (screen opens as soon as radiation drops below the closing threshold).
Radiation for position 0 – 1 200 W/m² 900 W/m² At radiation levels between Radiation below 100% and Radiation above 100%, the screen moves to a partial position. This value sets the radiation level at which the screen reaches the partial position defined by Screen position. Set to 0 to disable partial positioning (screen is either fully open or fully closed).
Screen position 0 – 100 % 80 % The partial screen position used when radiation is at the Radiation for position level. For example, 80 % means the screen is 80 % closed at that radiation level. Between the partial and full thresholds the position is interpolated proportionally.
GREENHOUSE — Screen A OutsideSettings
Open above windspeed12.0m/s
Open when rainingYes ▾

Screen A Outside — Settings explained

This screen only appears on installations with an outside (retractable) shade screen mounted above the greenhouse roof. It defines the weather conditions under which the outside screen must be retracted to prevent wind and rain damage.

SettingRangeDefaultWhat it does
Open above windspeed 0.0 – 33.0 m/s 12.0 m/s When wind speed exceeds this value the outside screen is retracted (opened) regardless of radiation, to prevent it from being torn by the wind. Once wind drops below this threshold, normal radiation control resumes.
Open when raining No / Yes Yes When set to Yes, the outside screen retracts whenever rain is detected. Rain pooling on a deployed outside screen can cause structural damage. Set to No only if the screen material is designed for outdoor use in rain.
GREENHOUSE — Screen A GapSettings
Min position0%
Temp difference5.0°C
Humidity difference humidity sensor only15%
Max Opening25%

Screen A Gap — Settings explained

When Screen A is closed, moisture and heat can build up underneath it. The gap control opens a small slot in the screen to release excess humidity or heat, without fully opening the screen and losing its shading or insulating effect.

SettingRangeDefaultWhat it does
Min position 0 – 100 % 0 % The screen will never close below this position, even when no gap is demanded. A small permanent gap (e.g. 5 %) ensures constant low-level ventilation under the screen at all times.
Temp difference 0.0 – 35.0 °C 5.0 °C The gap opens when the measured temperature exceeds the setpoint by more than this amount. This prevents overheating under a closed screen on a sunny day. The gap increases proportionally as the temperature excess grows, up to the Max Opening limit.
Humidity difference humidity sensor only 0 – 100 % 15 % The gap also opens when humidity exceeds the setpoint by more than this amount. High humidity under a closed screen promotes fungal disease, so a gap is opened to let moist air escape.
Max Opening 0 – 100 % 25 % The maximum gap the screen is allowed to open for temperature or humidity relief. Keeping this small (15–25 %) preserves the primary function of the screen while still allowing ventilation.
GREENHOUSE — Screen A EnergySettings
Time methodAstro ▾
Start time Absolute mode20:00h:m
Start to sunset Astro mode+00:00h:m
End time Absolute mode08:00h:m
End to sunrise Astro mode+00:00h:m
Max. opening time30min
At delta temp10.0°C
Opening step10%

Screen A Energy — Timing & Opening Settings

The energy screen closes at night to insulate the greenhouse and reduce heating costs. This screen configures when it closes and how it opens temporarily to release heat or humidity build-up during the night.

SettingRangeDefaultWhat it does
Time method Absolute / Astro Astro Determines how the energy screen window is defined. Astro uses offsets from sunset (start) and sunrise (end), so the screen automatically follows seasonal day length. Absolute uses fixed clock times that do not change with the season.
Start time / Start to sunset 00:00–23:59 / −4:00–+4:00 +00:00 (sunset) When the energy screen begins to close. In Astro mode, 0:00 means closing starts at sunset. A positive offset (e.g. +01:00) delays closing until one hour after sunset, useful if evening temperatures are still high.
End time / End to sunrise 00:00–23:59 / −4:00–+4:00 +00:00 (sunrise) When the energy screen opens at the end of the night. In Astro mode, 0:00 means the screen opens at sunrise. A negative offset (e.g. −01:00) opens the screen one hour before sunrise to allow the greenhouse to warm up gradually before daylight.
Max. opening time 0 – 240 min 30 min If the temperature or humidity under the closed screen rises too high, the screen opens briefly to ventilate. This setting limits how long each such opening event lasts. After this time the screen closes again even if conditions have not fully recovered.
At delta temp 0.0 – 25.0 °C 10.0 °C The screen opens for a ventilation event when the measured temperature exceeds the setpoint by more than this amount while the energy screen is closed. A larger value means the screen tolerates more overheat before opening. Set to 0 to allow opening at any positive temperature deviation.
Opening step 1 – 20 % 10 % How far the screen opens during each ventilation event. A small step (e.g. 5 %) releases heat gently; a larger step (e.g. 20 %) ventilates faster but loses more heat. After each step the controller waits to assess the effect before opening further.
GREENHOUSE — Screen A EnergySettings
Below outside temp10.0°C
Below radiation20W/m²

Screen A Energy — Conditions

These two settings define the weather conditions under which the energy screen is allowed to close. If either condition is not met, the screen stays open even during the configured energy window.

SettingRangeDefaultWhat it does
Below outside temp −15.0 – 45.0 °C 10.0 °C The energy screen only closes when the outside temperature is below this value. If it is warm outside, the insulating screen offers little benefit and may cause overheating. Lowering this threshold (e.g. to 5 °C) means the screen only closes on colder nights, saving heating energy when it matters most.
Below radiation 0 – 500 W/m² 20 W/m² The energy screen only closes when solar radiation is below this level. This prevents the screen from closing during the day even if the time window spans daylight hours. A value of 20 W/m² means the screen will not close while there is any meaningful sunlight.
Tip On an unexpectedly warm or sunny evening, these two conditions ensure the screen stays open so the greenhouse can cool naturally rather than being trapped under a closed insulating screen.
GREENHOUSE — Screen A-Gap EnergySettings
Temp difference5.0°C
Humidity difference humidity sensor only15%
Max Opening25%

Screen A Gap Energy — Settings explained

This screen works identically to the Screen A Gap (radiation) settings but applies specifically when the screen is closed in energy mode (night insulation). The gap settings for radiation and energy modes are independent, allowing different gap behaviour during the day and at night.

SettingRangeDefaultWhat it does
Temp difference 0.0 – 35.0 °C 5.0 °C Opens a gap in the energy screen when the temperature exceeds the setpoint by this amount during the night. A smaller gap is typically used at night (compared to daytime) to minimise heat loss while still preventing overheating.
Humidity difference humidity sensor only 0 – 100 % 15 % Opens a gap when humidity exceeds its setpoint by this amount during the night. Night humidity build-up under a closed energy screen is a common cause of fungal disease, so a small gap is important.
Max Opening 0 – 100 % 25 % The maximum gap allowed during energy mode. Keeping this small (10–25 %) preserves the insulating effect of the screen while still allowing moisture and heat to escape.
GREENHOUSE — Screen B-RadiationSettings
Start to sunrise+01:00h:m
End to sunset-01:00h:m
Radiation above 100%1 000W/m²
Radiation below 100%0W/m²
Radiation for position900W/m²
Screen position80%

Screen B Radiation — Settings explained

Screen B radiation control works identically to Screen A radiation control. All settings have the same meaning and ranges — refer to Screen A Radiation for full descriptions. Screen B is typically a second shade layer or a screen in a different greenhouse section, and can be configured independently with its own radiation thresholds.

GREENHOUSE — Screen B GapSettings
Min position0%
Temp difference5.0°C
Humidity difference humidity sensor only15%
Max Opening25%

Screen B Gap — Settings explained

Screen B gap control works identically to Screen A gap control. All settings have the same meaning and ranges — refer to Screen A Gap for full descriptions. Screen B can be given its own gap thresholds if it operates in a different zone or climate condition than Screen A.

9. HD Fogging

The high-pressure fog system sprays very fine water droplets into the greenhouse air. As the droplets evaporate they cool the air and raise humidity simultaneously. The system pulses the fog pump on and off — the ratio of on-time to off-time is controlled proportionally based on the demand. There are two trigger mechanisms: temperature-based (cool the air) and humidity-based (raise humidity), both operating independently within the same daily time window.

GREENHOUSE — HD FoggingSettings
Start to sunrise+01:00h:m
End to sunset-01:00h:m
Temperature trigger
Temperature diff5.0°C
Humidity limit active when Temp diff > 025%
Humidity trigger
Humidity diff4.0%
Temperature limit active when Humidity diff > 0-2.5°C

HD Fogging — Trigger Settings explained

The fog system has two independent trigger conditions. Either condition alone is enough to activate the fog pump. Each trigger has a guard limit on the other climate variable to prevent fogging in unsuitable conditions.

SettingRangeDefaultWhat it does
Start to sunrise −4:00 – +4:00 +01:00 The fogging system is only allowed to run within a daily time window. This offset defines when the window opens relative to sunrise. Fogging is typically only useful during daylight hours when evaporation is driven by heat and radiation.
End to sunset −4:00 – +4:00 −01:00 When the daily fogging window closes, relative to sunset. Fogging before sunset allows moisture to dry before the cooler night air arrives.
Temperature diff −10.0 – 35.0 °C 5.0 °C The temperature trigger activates fogging when the measured inside temperature exceeds the current setpoint by more than this amount. For example, with a setpoint of 24 °C and a diff of 5 °C, fogging starts when the temperature reaches 29 °C. Set to 0 (Off) to disable temperature-based triggering entirely.
Humidity limit active when Temp diff > 0 0 – 50 % 25 % A safety guard for the temperature trigger. Even if the temperature is above the trigger threshold, fogging will not start if the humidity is already within this percentage below its setpoint. This prevents over-humidification when trying to cool an already humid greenhouse.
Humidity diff 0.0 – 10.0 % 4.0 % The humidity trigger activates fogging when the measured humidity falls more than this percentage below the humidity setpoint. For example, with a setpoint of 80 % and a diff of 4 %, fogging starts when humidity drops to 76 %. Set to 0 (Off) to disable humidity-based triggering.
Temperature limit active when Humidity diff > 0 −20.0 – 0.0 °C −2.5 °C A safety guard for the humidity trigger. Fogging will not start if the temperature is already this many degrees below the setpoint, even if humidity is low. Fogging into a cold greenhouse causes condensation problems rather than solving humidity issues.
GREENHOUSE — HD FoggingSettings
Radiation limit800W/m²
Min pulse time10s
Max pulse time20s
P-Band50%

HD Fogging — System Settings explained

These settings define how the fog pump behaves once a trigger condition is active. The pump does not run continuously — it pulses on and off, with the on-time increasing proportionally as demand grows.

SettingRangeDefaultWhat it does
Radiation limit 0 – 1 200 W/m² 800 W/m² The fog system only operates when solar radiation is above this level. High radiation provides the energy to evaporate the fine droplets — without sufficient radiation the droplets may not evaporate quickly enough, causing condensation on plants and structures. On overcast days when radiation is low, fogging is suppressed automatically.
Min pulse time 1 s – max 10 s The minimum duration of each pump-on pulse. Even at low demand, the pump runs for at least this many seconds to ensure a complete fog burst is produced. Very short pulses can be ineffective if the nozzles need time to build pressure.
Max pulse time 1 s – max 20 s The maximum duration of each pump-on pulse at full demand. The actual pulse time scales between Min and Max proportionally with the demand level. A wider range between Min and Max gives finer control over the amount of water delivered.
P-Band 1 – 1 000 % 50 % The proportional band of the fog controller. At a temperature or humidity error equal to the P-Band value, the fog pump runs at 100 % duty (maximum pulse time). A smaller P-Band gives a more aggressive response to small deviations; a larger P-Band gives a gentler, more gradual response.
10. Light Row Groups

Individual light rows (circuits) can be assigned to groups 1–4. The active group is selected on the main Light settings screen. This allows pre-configured power levels — for example Group 1 = full intensity, Group 2 = 50 % intensity — that can be switched quickly without re-programming each row.

GREENHOUSE — Light RowSettings
Group 1100% ▾
Group 250% ▾
Group 3Off ▾
Group 4Off ▾

Light Row — Groups 1–4

Each row that is wired to this light controller appears here. For each row you select which power group it belongs to. Rows set to the same group switch on and off together. Only rows physically connected to this controller appear on the screen.

SettingOptionsDefaultWhat it does
Group 1 – 4 (per row) Off / 25 % / 50 % / 75 % / 100 % Off Assigns this light row to a power group and sets its intensity level within that group. Off means the row is never switched on by the lighting programme. Selecting a percentage (25–100 %) assigns the row to the corresponding power group. When the active group is selected on the main Light screen, all rows in that group switch on at their configured intensity.
Example setup Assign rows 1–4 to Group 1 at 100 %. Assign rows 1–2 to Group 2 at 100 % and rows 3–4 to Off. On the Light screen, selecting Group 1 turns on all four rows (full power), while selecting Group 2 turns on only rows 1 and 2 (half the greenhouse).
GREENHOUSE — Light RowSettings
Group 5Off ▾
Group 6Off ▾
Group 7Off ▾
Group 8Off ▾

Light Row — Groups 5–8

This screen shows the remaining light rows (if more than four are installed). The settings work identically to Groups 1–4 — refer to that screen for a full description. Rows only appear if they are physically connected to the controller.

11. Alarms

The alarm screen configures which conditions trigger notifications. Each alarm can be set to Off (no notification), Warning (logged but no output), or Alarm (logged and activates the alarm output/relay). Only alarms for hardware that is actually installed appear on the screen.

GREENHOUSE — AlarmSettings
Temperature alarm temperature sensor onlyAlarm ▾
Sensor defectAlarm ▾
CO2 too high CO2 sensor onlyWarning ▾
Humidity alarm humidity sensor onlyOff ▾

Alarm — Settings explained

Each alarm condition can be independently configured. The alarm thresholds themselves (e.g. how many degrees above setpoint triggers a temperature alarm) are set elsewhere — typically on the relevant settings screen such as Temperature Periods. This screen only controls what happens when the threshold is crossed.

AlarmOptionsDefaultWhat it monitors
Temperature alarm temperature sensor only Off / Warning / Alarm Off Activates when the measured temperature deviates from the setpoint by more than the Rel temp alarm value configured on the Temperature Periods screen. Use Alarm to trigger the external alarm output (relay) so staff are notified, for example by a SMS module or audible buzzer.
Sensor defect Off / Warning / Alarm Off Activates when any connected sensor returns an out-of-range or disconnected reading. A faulty sensor causes the controller to work without feedback, which may result in incorrect heating or ventilation. This alarm should generally always be enabled.
CO2 too high CO2 sensor only Off / Warning / Alarm Off Activates when the measured CO2 concentration exceeds the CO2 Alarm level set on the CO2 System screen. Excessively high CO2 can indicate a dosing valve stuck open or inadequate ventilation, and high levels may be harmful to workers inside the greenhouse.
Humidity alarm humidity sensor only Off / Warning / Alarm Off Activates when the measured humidity deviates from the setpoint by more than the Rel humidity alarm value configured on the Temperature Periods screen. Persistent high humidity promotes fungal disease; persistent low humidity stresses the crop.
Alarm output levels
Off — The condition is completely ignored. No log entry, no output.
Warning — The condition is logged in the alarm list and shown on the dashboard, but the external alarm relay/output is not activated.
Alarm — The condition is logged and the external alarm output is activated, triggering any connected notification device (buzzer, SMS module, etc.).